R8-YST4N DC CURRENT OUTPUT MODULE

Share on FacebookShare on Google+Tweet about this on TwitterShare on LinkedIn

Tình trạng: In stock

Contact: 0989649965

R8-YST4N Remote I/O R8 Series DC CURRENT OUTPUT MODULE

Số lượt xem: 1436

Detail

·Some details are not shown. Please refer to specification sheets for all information.

R8-YST4N

Remote I/O R8 Series

DC CURRENT OUTPUT MODULE
(4 points, non-isolated, Tension clamp terminal block)

Functions & Features
• 4 channels for DC current output, compact size remote I/O module
• 8 pins tension clamp connector
• Output range adjustment with DIP switch or PC configurator

MODEL: R8–YST4N[1]

ORDERING INFORMATION
• Code number: R8-YST4N[1]
Specify a code from below for [1].
  (e.g. R8-YST4N/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS
• PC configurator software (model: R8CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS
Connection
 • Output: Tension clamp
    Applicable wire size: 0.2 - 1.5 mm2
    Stripped length: 10 mm
 • Excitation supply, internal bus:
    Connected to internal bus connector
 • Internal power: Via bus connector
Isolation: Output to exc. supply to internal bus or internal power
Output range: Selectable with the side DIP SW
Module address: With DIP switch
Output at the loss of communication: Selectable with the side DIP SW
Terminating resistor: Built-in (DIP Switch, default: disable)
Configuration mode: With DIP switches on the side panel
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.
Output status indicators: Red LED; Refer to the instruction manual.

OUTPUT
Output range: Selectable between 0 – 20mA DC
Operational range: -5 – +105 % (in percentage of output range) ≤ 0 mA DC
Load resistance: ≤ 350Ω

INSTALLATION
Max. current consumption: 70 mA
Exc. supply current consumption: 90 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 120 g (0.26 lb)

PERFORMANCE
Conversion accuracy (in percentage of output range)
±0.08 % (@ output range 0 - 20 mA)
Conversion accuracy is inversely proportional to output span.
  Conversion accuracy computation example:
  When output range is 4 - 20 mA: conversion accuracy = output span standard value (20 mA) ÷ output span (16 mA) × 0.08(%) = 0.1 (%).
output span standard value is the same as the span at output range 0 - 20 mA DC.
Conversion rate: 4 msec.
Output circuit time constant: ≤ 1 msec. (0 → 90 %)
Data range: 0 – 10000 of the output range
Data allocation: 2
Module addresses in use: 2
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
  1500 V AC @ 1 minute (output to exc. supply to internal bus or internal power to ground)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

EXTERNAL VIEW

OPERATING MODE SETTING
(*) Factory setting
Caution ! - SW2-2, 2-3, 2-4, 2-7 are unused.  Be sure to turn off unused ones.

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1064650
Online: 26
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965