R8-PA4 TOTALIZED PULSE INPUT MODULE, 4 points

Share on FacebookShare on Google+Tweet about this on TwitterShare on LinkedIn

Tình trạng: In stock

Contact: 0989649965

R8-PA4 Remote I/O R8 Series TOTALIZED PULSE INPUT MODULE, 4 points (NPN / PNP / Voltage pulse input)

Số lượt xem: 1457

Detail

·Some details are not shown. Please refer to specification sheets for all information.

R8-PA4

Remote I/O R8 Series

TOTALIZED PULSE INPUT MODULE, 4 points
(NPN / PNP / Voltage pulse input)

Functions & Features
• Space-saving remote I/O module of 4 points input pulse counter

MODEL: R8–PA4[1][2]

ORDERING INFORMATION
• Code number: R8-PA4-[1][2]
Specify a code from below for each [1] and [2].
 (e.g. R8-PA4A/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] INPUT
A: NPN input
B: PNP input
C: Voltage pulse iput

[2] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS
• PC configurator software (model: R8CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS
Connection
 
Input: 4-pin e-CON connector
  PWB connector XN2D-1474-S002 (Omron)
  Recommended cable connector XN2A-1470 (Omron)
  Applicable wire size 0.08 mm2 (AWG28) - 0.5 mm2 (AWG20)
  Outer sheath diameter: max. 1.5 dia
  (The cable connector is not included in the package.
   Refer to the specifications of the product.)
 Excitation supply, internal bus:
  Connected to internal bus connector
 Internal power: Supplied from internal bus connector
Isolation: Input or exc. supply to internal bus or internal power
Module address: With rotary switch
Terminating resistor: Built-in (DIP Switch, default: disable)
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.
Input status indicator: Green LED; Refer to the instruction manual.

INPUT SPECIFICATIONS
Common: Positive or negative common (NPN/PNP) per 4 points
Number of inputs: 4
I/O status indicator: LED turns on with closed contact.
NPN/PNP input (internal supply with excitation supply input from network power module)
  Rated load voltage: 24 V DC ±10 %; ripple 5 %p-p max.
  ON voltage / ON resistance: ≤ 4 V (input terminal to COM) / ≤ 900 Ω
  OFF voltage / OFF resistance: ≥ 16 V (input terminal to COM) / ≥ 10 kΩ
Voltage pulse input
  Max. input voltage amplitude
: 24 V DC + ≤ 10 %
  ON voltage / ON current: ≥ 16 V DC (input terminal to COM) / ≥ 3.7 mA
  OFF voltage / OFF current: ≤ 5 V DC (input terminal to COM) / ≤ 1 mA
  Input current: ≤ 5.5 mA / point (@24 V DC)
  Input resistance: Approx. 4.4 kΩ
ON delay: ≤ 2.0 msec.
OFF delay: ≤ 2.0 msec.
Max. Frequency: 100 Hz
Minimum ON/OFF pulse requirements: 5 ms
Accumulated pulse count: 0 - 4 294 967 295
Max. accumulable pulse: 1 - 4,294,967,295 (factory setting: 4,294,967,295)
Overflow reset value
: 0 or 1 (factory setting: 0)

INSTALLATION
Max. current consumption: 80 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 60 g (2.12 oz)

PERFORMANCE
Data allocation: 2
Module addresses in use: 4
Power output (input terminal): Rated curent 0.1A DC per channel
(rated current 3 A for internal fuse (slow blow fuse i2t (A2sec) max. 0.31)
Total 0.4 A DC
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input or exc. supply to internal bus or internal power to ground)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

EXTERNAL VIEW

OPERATING MODE SETTING

(*) Factory setting

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1064866
Online: 22
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965