R5-DC4 DISCRETE OUTPUT MODULE

Share on FacebookShare on Google+Tweet about this on TwitterShare on LinkedIn

Tình trạng: In stock

Contact: 0989649965

R5-DC4 Remote I/O R5 Series DISCRETE OUTPUT MODULE (relay contact output, 4 points)

Số lượt xem: 1461

Detail

·Some details are not shown. Please refer to specification sheets for all information.

R5-DC4

Remote I/O R5 Series

DISCRETE OUTPUT MODULE
(relay contact output, 4 points)

MODEL: R5–DC4[1][2]

ORDERING INFORMATION
• Code number: R5-DC4[1][2]
Specify a code from below for each [1] and [2].
 (e.g. R5-DC4W/Q)
• Specify the specification for option code /Q
 (e.g. /C01)

NO. OF CHANNELS
4: 4-point outputs

[1] COMMUNICATION MODE
S: Single
W: Dual

[2] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS
Connection
  Internal bus: Via the Installation Base (model: R5-BS)
  Output: Euro type connector terminal
  (Applicable wire size: 0.2 – 2.5 mm2 (AWG24 - 12),
   stripped length 7 mm)
  Internal power: Via the base (model: R5-BS)
Isolation: Do1 or Do2 to Do3 or Do4  to internal bus or internal power
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
Output status indicator: Red LED; turns on with the outputs ON.

OUTPUT SPECIFICATIONS
Output: Relay contact, 4 points
Common: Every 2 points
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (rate 300/min.)
When driving an inductive load, external contact protection and noise quenching recommended.

INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS)
Weight: 100 g (3.53 oz)

PERFORMANCE
Data allocation: 1
Response time: ≤ 0.1 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (Do 1 or Do 2 to Do 3 or Do 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive 
 EN 61010-1,EN 61010-2-201
 Measurement Category II (output)
 Pollution Degree 2
 Contact output to internal bus or internal power – Basic insulation (300 V)
RoHS Directive
  EN 50581

FUNCTIONS
Output hold function:
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
If both are in error, the module holds the signal and stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is established and normal data is received.

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1064138
Online: 28
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965