R3Y-PA16 TOTALIZED PULSE INPUT MODULE

Share on FacebookShare on Google+Tweet about this on TwitterShare on LinkedIn

Tình trạng: In stock

Contact: 0989649965

R3Y-PA16 Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE (Pi 16 points; connector type)

Số lượt xem: 1642

Detail

·Some details are not shown. Please refer to specification sheets for all information.

R3Y-PA16

Remote I/O R3 Series

TOTALIZED PULSE INPUT MODULE
(Pi 16 points; connector type)

MODEL: R3Y–PA16[1][2]

ORDERING INFORMATION
• Code number: R3Y-PA16[1][2]
Specify a code from below for each [1] and [2].
 (e.g. R3Y-PA16W/A/CE/Q)
• Specify the specification for option code /Q
 (e.g. /C01/SET)

NO. OF CHANNELS
16: 16

[1] COMMUNICATION MODE
S: Single
W: Dual

[2] OPTIONS (multiple selections)
Excitation
Blank: Internal (negative common)
/A: External (24 V DC, negative common)
Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-8389)

GENERAL SPECIFICATIONS
Connection
 Internal bus
: Via the Installation Base (model: R3-BSx)
 Input: 40-pin connector (Fujitsu Model FCN-365P040-AU)
 Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Input to internal bus or internal power
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with the excitation abnormality;
Green in normal operating conditions.
Input status indicator: Red LED; turns on with the inputs supplied.
Count reset: Via DIP switches on the side

INPUT SPECIFICATIONS
Number of input: 16 points
Input resistance: 6 kΩ
Common: Negative commons, all points
Maximum frequency: 100 Hz (ON/OFF time ≥ 5 msec.)
This unit is designed to be able to accept a frequency up to 100 Hz, however, ‘chattering’ contact must be avoided for accurate measuring of such high frequency. Use mercury relays or similar ones that do not cause any chattering.
Totalized pulse range: 1 – 10000 (‘0’ at reset)
Max. pulse range selectable from 1 to 65535 using the R3CON PC Configurator Software. Refer to the R3CON Users Manual for detailed information.
Count at overflow: Reset and restart at ‘1.’
■ R3-PA16x (internal excitation)
Sensing voltage: 13 V DC (max. 24 V with no load)
ON current: ≥ 1.5 mA (≤ 1.5 kΩ)
OFF current: ≤ 0.75 mA (≥ 18 kΩ)
■ R3-PA16x/A (external excitation)
Sensing voltage: 24 V DC
ON current: ≥ 1.5 mA (≤ 12 kΩ)
OFF current: ≤ 0.75 mA (≥ 36 kΩ)

INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE
Data allocation: 16
Current consumption:
 R3Y-PA16x: 100 mA
 R3Y-PA16x/A: 80 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute
(input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

FUNCTIONS
■ MANUAL COUNT RESET
1) Remove Network Module or its cables and interrupt communication with other devices.
2) Turn ON the Count Reset SW (DIP SW3-1).
3) Return the module to the base and turn the power supply on.
4) ERR LED turns on and the module starts resetting its counter. When the resetting is complete, the LED light turns to green. DO NOT remove the power while the red light is on.The RUN LED starts blinking at the same time.
5) After the green LED is confirmed, turn the power supply off.
6) Turn OFF the Count Reset SW (DIP SW3-1).
7) Return the Network module onto the base and turn the power supply on.
Note: Count Reset SW must be turned OFF after this procedure because the module does not start counting with ON state.
■ REMOTE COUNT RESET INPUT 
With the Count Reset Input SW (DIP SW3-3) turned ON, the Pi 16 pulse input can be used to remotely reset the count values.
SW3-3 = OFF: Pi 16 is used as a pulse input.
SW3-3 = ON: Pi 16 is used to reset the count values for the Pi 1 through Pi 15. One pulse supplied at the Pi 16 will be recognized as a reset signal.
■ REMOTE COUNT RESET OPERATION
1) ERR LED turns on (red color) when the reset signal is received.
2) In 1 second, the module starts resetting its counter.
When the resetting is complete, the LED light turns to green.
3) After 1 second, ERR LED turns back to the state before the reset signal has been received.
Note: Reset signals received while the module is processing (1) through (3) are ignored.

EXTERNAL VIEW

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

INPUT CONNECTOR (40-pin)

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1064592
Online: 27
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965