R3-US4 UNIVERSAL INPUT MODULE

Share on FacebookShare on Google+Tweet about this on TwitterShare on LinkedIn

Tình trạng: In stock

Contact: 0989649965

R3-US4 Remote I/O R3 Series UNIVERSAL INPUT MODULE (4 points, isolated)

Số lượt xem: 1655

Detail

·Some details are not shown. Please refer to specification sheets for all information.

R3-US4

Remote I/O R3 Series

UNIVERSAL INPUT MODULE
(4 points, isolated)

MODEL: R3-US4[1][2]

ORDERING INFORMATION
Code number: R3-US4[1][2]
Specify a code from below for each [1] and [2].
(e.g. R3-US4W/A/Q)
• Specify the specification for option code /Q
  (e.g. /C01/SET)
Factory default setting
Input
: DC voltage, ±12 V
Temperature unit: °C
Burnout: Upscale
CJC: ON

NO. OF CHANNELS
4: 4

[1] COMMUNICATION MODE
S: Single
W: Dual

[2] OPTIONS (multiple selections)
Temperature input accuracy
blank: Standard
/A: High accuracy
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-8449)

RELATED PRODUCTS
• PC configurator software (model: R3CON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS
Connection
 Internal bus: Via the Installation Base (model: R3-BSx)
 Input: M3 separable screw terminal (torque 0.5 N·m)
 Internal power: Via the Installation Base
 (model: R3-BSx)
Screw terminal: Nickel-plated steel
Isolation: Input 1 to input 2 to input 3 to input 4 to internal bus or internal power
Input range: Selectable with configuration software (model: R3CON)
Temperature unit (Thermocouple or RTD input): Selectable with PC configuration software (model: R3CON)
Burnout for T/C and RTD input: Upscale, downscale or no burnout selectable with PC configurator software
Select “No burnout” to minimize the measuring errors caused by the sensor/wire resistance and the burnout sensing current. With RTD input, the signal may go transiently to the opposite direction from the burnout setting.
Burnout is not detected at DC voltage or potentiometer input. The burnout sensing current is turned off.
Cold junction compensation (CJC) for T/C input: CJC is selectable whether enabled or disabled by using the PC configurator software. The cold junction sensor is mounted to the terminal of each channel.
A/D conversion mode: (Temp. input accuracy: standard)
Low or middle conversion rate selectable with PC configurator software
RUN indicator: Bi-color (red/green) LED;
Red when connected to a host PC/PLC via internal bus A Green when connected to a host PC/PLC via internal bus B (R3-US4W only)
Amber when connected to a host PC/PLC via both buses (R3-US4W only)
ERR indicator: Bi-color (red/green) LED;
Red with the input circuit abnormality
Green in normal operating conditions

INPUT SPECIFICATIONS
■ DC Voltage
Input resistance
: ≥ 600 kΩ
Except the case that the input voltage is out of -1.3 to +1.3 V for ±60 mV, ±125 mV, ±250 mV, ±500 mV and ±1000 mV ranges
Input range: See Table 1.
■ Thermocouple
Input resistance: ≥ 600 kΩ
Input range: See Table 2-1 and 2-2. (standard accuracy), see Table 5 (high accuracy).
Burnout sensing
  Upscale
: ≤ 130 nA
  Downscale: ≤ 220 nA
  No burnout: ≤ 10 nA
■ RTD (3-wire)
Excitation
: 1.25 V / (1.31 kΩ + load resistance across the terminals A – C)
Input range: See Table 3 (standard accuracy), see Table 6 (high accuracy).
Allowable leadwire resistance: 20 Ω per wire
■ Potentiometer
Excitation: 1.25 V / (1.31 kΩ + total resistance)
Total resistance: See Table 4.

INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 210 g (0.46 lb)

PERFORMANCE
Conversion accuracy: See Table 1 through 6.
Conversion rate: See Table 1 through 6.
Data range
  DC Voltage or potentiometer
: 0 to 10000 for input range
Thermocouple or RTD (standard accuracy)
  °C, absolute temperature
: Engineering unit value × 10 (integer)
  °F: Engineering unit value (integer)
Thermocouple or RTD (high accuracy)
  °C
: Engineering unit value × 100 (integer)
  °F: Engineering unit value × 10 (integer)
  (Absolute temperature not available for high accuracy)
Data allocation: 4
Current consumption: 60 mA
Cold junction compensation error: ±1.0°C maximum (at 25°C ±10°C); ±1.8°F maximum (at 77°F ±18°F)
(±1.5°C or ±2.7°F for R, S, PR)
Cold junction compensation is not available for B thermocouple.
Temp. coefficient: See Tables 1 through 6.
Burnout response
  Thermocouple K (CA), E (CRC), J (IC), N, L, P (Platinel II):
  ≤ 20 sec. for upscale
  ≤ 10 sec. for downscale
  RTD or the other thermocouple types: ≤ 10 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V peak @ 1 minute (input 1 to input 2 to input 3 to input 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

INPUT TYPE, RANGE,CONVERSION ACCURACY & TEMPERATURE COEFFICIENT

EXTERNAL VIEW

INPUT DATA DESCRIPTIONS

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1080270
Online: 26
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965