R3-NCIE1 Remote I/O R3 Series NETWORK INTERFACE MODULE (CC-Link IE Field network)

Số lượt xem: 1580

Detail

·Some details are not shown. Please refer to specification sheets for all information.

R3-NCIE1

Remote I/O R3 Series

NETWORK INTERFACE MODULE
(CC-Link IE Field network)

MODEL: R3-NCIE1[1]

ORDERING INFORMATION
• Code number: R3-NCIE1[1]
Specify a code from below for [1].
  (e.g. R3-NCIE1/CE/W/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Mitsubishi PLC Redundant System
blank: Without
/W: With
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS
• PC configurator software (model: R3CON)
Downloadable at M-System’s web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)

GENERAL SPECIFICATIONS
Connection
  CC-Link IE Field
: RJ-45 Modular Jack
  Internal bus: Via the Installation Base (model: R3-BSx)
  Internal power: Via the Installation Base (model: R3-BSx)
  RUN contact output: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal: Nickel-plated steel
Isolation: CC-Link IE Field to internal bus or internal power to RUN contact output 
Input error data setting: Input value setting at input module error with side DIP SW
Dual communication setting: Set with the side DIP switch
Data allocation setting: Set with the side DIP switch
RUN indicator: Green LED ON at normal operating
ERR indicator: Red LED ON at abnormal node
 RUN CONTACT OUTPUT
RUN contact: Turns ON while the green RUN LED is ON (ON in normal operation).
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.

CC-Link IE Field COMMUNICATION
Protocol: IEEE 802.3
Transmission type: 1000BASE-T
Communication speed: 1 Gbps
Network cable: Cable conformed to CC-Link IE Field
Double shielded twist pair cable (CAT5e)
RJ-45 connector
Network topology: Line, star and ring
Max. number stations: 120 (Total slave station)
(Number of max. connectable slaves may vary depending on the master module. Refer to the instruction manual of the master module)
Max. station-to-station distance: 100 m
Station type: Remote device station
Link device: RX/RY 128 points, RWw/RWr 64 points
NetWork No.: 1 to 239 (factory default: 1)

INSTALLATION
Current consumption: 170 mA max.
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 190 g (0.42 lb)

PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (CC-Link IE Field to internal bus or internal power to RUN contact output)
1500 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

EXTERNAL VIEW

TRANSMISSION DATA DESCRIPTIONS
Number of transmission data (data allocation) for each I/O module is set with the DIP switch on the side of the unit. Data allocation is assigned from slot 1 in sequence.
Keep number of transmission data of I/O module under 64, because max. number of transmission data is 64 per a node.
Station type: Remote device station
Link device: RX/RY 128points, RWw/RWr 64points
E.g. I/O data is assigned as shown below in the case of following configuration.

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.

■ OPERATION IN CASE OF A COMMUNICATION ERROR WITH I/O MODULES
When the communication between the network module and the I/O modules is lost due to an error in an input module, the last process values are held until the communication is re-established.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1069125
Online: 16
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965