R3-GFL1 FL-net INTERFACE MODULE
Tình trạng: In stock
Contact: 0989649965
R3-GFL1 Remote I/O R3 Series FL-net INTERFACE MODULE (OPCN-2, Ver.2.0 supported)
Số lượt xem: 1570
Detail
·Some details are not shown. Please refer to specification sheets for all information.
R3-GFL1
Remote I/O R3 Series
FL-net INTERFACE MODULE
(OPCN-2, Ver.2.0 supported)
Functions & Features
• Usable as a gateway between different protocols combined with R3 interface modules
• FL-net (OPCN-2), Ethernet based, controller level network, compatible remote I/O
• 10 Mbps/100 Mbps cyclic transmission for the maximum of 4k bits + 256 words (1 word = 16 bits) allows data shared among the devices connected to the bus
• FL-net bus extended to max. 500 meters, up to 2.5 kilometers with a repeater
• No need of ladder programming
Typical Applications
• A gateway between FL-net and Modbus
MODEL: R3-GFL1S[1]
ORDERING INFORMATION
• Code number: R3-GFL1S[1]
Specify a code from below for [1].
(e.g. R3-GFL1S/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
COMMUNICATION MODE
S: Single
[1] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
FUNCTIONS & FEATURES
■ R3-GFL1 enables the other interface module to access field signals as virtual I/O data via FL-net. No ladder programming is required to assign these I/O signals.
■ Any PC or PLC compatible with FL-net, up to 254 nodes, can retrieve the updated data by accessing the common memory without interfering with the communication traffic.
■ Analog and discrete input signals cyclically transmitted from other devices can be output as virtual analog signal.
The FL-net Configuration Builder software (model: R3-NFLBLD) is used to assign these virtual analog signals on the common memory in the bit or word units.
■ Request/Response type message communication, accessing I/O data only when necessary, is also possible.
CAUTION !
• FL-net standard requires a dedicated Ethernet bus for the FL-net compatible devices. Connecting the R3-GFL1 to a general-purpose LAN, or connecting a general-purpose TCP/IP device to FL-net is Not allowed.
• FL-net uses UDP/IP protocol for transmission. ISDN, ADSL or similar types of LAN are Not to be used.
RELATED PRODUCTS
• FL-net configuration builder (Model: R3-NFLBLD)
Downloadable at M-System’s web site.
• Interface module (model: R3-NC1, R3-NC3, R3-NDx,
R3-NE1, R3-NM1, R3-NM4, R3-NP1)
Firmware version V2.00 or later
• Interface module (model: R3-NM3, R3-NML3)
Firmware version V1.00 or later
• Paperless recorder (model: 73VR3100)
GENERAL SPECIFICATIONS
Connection
Network: RJ-45 connector
Internal bus: Via the Installation Base (model: R3-BSx)
Internal power: Via the Installation Base (model: R3-BSx)
RUN contact output: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm)
RUN/CFG selector: Toggle switch; RUN or Configuration
Isolation: Ethernet to internal bus or internal power to RUN contact output
Indicator LEDs
RUN: Green LED turns on when the CPU, internal bus and
field bus on the other interface module are in normal
conditions.
ERR: Red LED turns on in an abnormality of the system.
LNK: Red LED turns on while the R3-GFL1 is participating
FL-net (normal communication)
HER: Red LED turns on in an abnormality of I/O data.
PER: Red LED blinks on with the parameter setting error.
CFG: Red LED blinks in high speed at the startup; blinks in
low speed while the builder software is used.
TX: Green LED turns on while transmitting.
RX: Amber LED turns on while receiving.
Module allocation: Set with the side DIP switch.
■ RUN CONTACT OUTPUT
RUN contact: Relay turns on when the CPU, the internal bus function and the field bus on the other interface module are in normal conditions.
Rated load: 250 V AC @0.5A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(< 50 V AC, < 75 V DC for EU conformity)
Maximum switching voltage: 250 V AC or 220 V DC
Maximum switching power: 62.5 VA or 60 W
Minimum load: 10 mV DC @ 1 mA
Mechanical life: 5 × 107 cycles (rate 300/min.)
When driving an inductive load, external contact protection and noise quenching are recommended.
FL-net SPECIFICATIONS
FL-net: Ver.2.0 supported
Physical layer standard: IEEE 802.3u
Data link layer: 10BASE-T / 100BASE-TX
Baud rate: 10 / 100 Mbps, Auto Negotiation
Protocol: FL-net (OPCN-2) (UDP/IP)
Transmission media: 10BASE-T (STP cable, category 5)
100BASE-TX (STP cable, category 5e)
Max. segment length: 100 meters
Max. number of nodes: 254
IP address: FL-net Configuration Builder is used to set up the IP address and the network address.
Factory setting:
192.168.250.1 (IP address)
255.255.255.0 (network address)
Max. cyclic data size:
8 k bits (area 1) + 8 k words (area 2) / system
4 k bits (area 1) + 256 words (area 2) / node
Max. message data size: 1024 bytes (per transmission cycle)
Performance (2k bits + 2k words / node, 32 nodes in total)
Token cycle time: 50 milliseconds (1.56 milliseconds/ node in average)
Message transmission time: 500 milliseconds (1 : 1 unidirectional message)
INSTALLATION
Current consumption: 150 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
PERFORMANCE
Data allocation: 16 × n (Module allocation: 1 to 8)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(Ethernet to internal bus or internal power to RUN contact output)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
FL-net DESCRIPTIONS
■ CYCLIC TRANSMISSION
• Transmitting virtual I/O value, this module's information and node error of signal source.
• Supplying common memory word data transmitted from another devices as virtual output.
• If the node that this module is accessing has been removed from the common memory, the operations “Hold output” and “Clear Output” are selectable.
■ MESSAGE TRANSMISSION
The module supports the FL-net defined functions listed in the following table. Only the server function is supported.
Server function allows the module to build a response frame to a request message.
Client function allows the module to transmit a request message and to receive its response frame.
PC REQUIREMENTS (provided by the user)
The following PC environment is required to run the R3-NFLBLD program.
Operating system: Windows 7 (32-bit/64-bit) or Windows 10 (32-bit/64-bit)
Screen area: 1024 by 768 pixels
LAN card: Required to connect to Ethernet
EXTERNAL VIEW
TRANSMISSION DATA DESCRIPTIONS
Use the DIP SW located at the side of the module to specify module allocation.
1 module is equivalent to 1 I/O module with 16 words analog input and 16 words analog output. Max. 8 modules (128 words input, 128 words output) transmission is available. R3-GFL1 seems as if max. 8 I/O modules are mounted to 8 slots via FL-net.
The input of the module is processed as follows.
[FL-net Communication] --> [R3-GFL1 Module] --> [R3 Base] --> [R3 Communication Module]
The data set with output tab of R3-NFLBLD to input is transmitted to R3 communication module. Output is reversed. The data set with transmitting area 1 and transmitting area 2 is transmitted to FL-net.
Note: Do not mount any modules in the slots which are occupied by virtual modules. If a real I/O module is mounted in the slot, an internal bus error occurs. Max. 16 real I/O modules and virtual modules are available. The interface module can not read the data for more than 16 modules.
■ WHEN R3-GFL1 IS MOUNTED TO SLOT 2 (4 modules)
In practice, I/O modules are mounted to slot 1 and slot 2. The R3-NE1 in slot 7 recognizes the R3-SV4 in slot 1 directly. However, the R3-NE1 recognizes the R3-GFL1 in slot 2 as if 4 modules are mounted to from slot 2 to 5.
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm (inch)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
SYSTEM CONFIGURATION EXAMPLES
M-System Co., Ltd.
Products
-
R1MS-GH3 THERMOCOUPLE & DC INPUT MODULE
R1MS-GH3 Remote I/O R1M Series THERMOCOUPLE & DC INPUT MODULE (8 points, isolated)
-
R1M-P4/MSR PC RECORDER
-
R1M-P4 Remote I/O R1M Series
R1M-P4 Remote I/O R1M Series CONTACT I/O MODULE (4 totalized counter inputs, 8 contact inputs and outputs)
-
R1M-J3/MSR PC Recorders R1M Series
R1M-J3/MSR PC Recorders R1M Series PC RECORDER (RTD or potentiometer input, 8 points)
-
R1M-J3 Remote I/O R1M Series
R1M-J3 Remote I/O R1M Series RTD & POTENTIOMETER INPUT MODULE (8 points)
-
R1M-GH/MSR PC Recorders R1M Series
R1M-GH/MSR PC Recorders R1M Series PC RECORDER (thermocouple or DC input, 16 points)
-
R1MS-GH3/MSR PC Recorders R1M Series
R1MS-GH3/MSR PC Recorders R1M Series PC RECORDER
-
R1D-GH2 THERMOCOUPLE & DC INPUT MODULE
R1D-GH2 Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE (16 points; DeviceNet)
-
R1C-GH THERMOCOUPLE & DC INPUT MODULE
R1C-GH Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE (16 points; CC-Link Ver.1.10/Ver.2.00)
PRODUCTS LIST
- Signal Conditioners
- 2-wire Signal Conditioners
- Power Transducers
- Indicators
- Tower Lights
- Limit Alarms
- Gateway, Remote IO
- Paperless Recording System
- PC Recorder
- Web Data Loggers
- PID Control Components
- BA&Energy Monitoring Components
- Temperature Controllers
- Electric Actuators
- Lightning Surge Protectors
STATISTIC
Visitor: 1069023Online: 26