R3-DC64A DISCRETE OUTPUT MODULE

Share on FacebookShare on Google+Tweet about this on TwitterShare on LinkedIn

Tình trạng: In stock

Contact: 0989649965

R3-DC64A Remote I/O R3 Series DISCRETE OUTPUT MODULE (Do 64 points; open collector)

Số lượt xem: 1590

Detail

·Some details are not shown. Please refer to specification sheets for all information.

R3-DC64A

Remote I/O R3 Series

DISCRETE OUTPUT MODULE
(Do 64 points; open collector)

MODEL: R3–DC64A[1][2]

ORDERING INFORMATION
• Code number: R3-DC64A[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3-DC64AW/CE/Q) 
• Specify the specification for option code /Q
  (e.g. /C01)

NO. OF CHANNELS
64: 64

OUTPUT
A: Open collector

[1] COMMUNICATION MODE
S: Single
W: Dual

[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS
Connection
  Internal bus
: Via the Installation Base (model: R3-BSx)
  Output: 40-pin connector (Fujitsu FCN-365P040-AU)
  Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Do11 thru Do18 to Do21 thru Do28 to Do31 thru Do38 to Do41 thru Do48 to Do51 thru Do58 to Do61 thru Do68 to Do71 thru Do78 to Do81 thru Do88 to internal bus or internal power
Output hold setting: Setting for communication error with side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED turns on in normal operating conditions.
Output status indicator: Red LED; turns on with the output ON.
Group selector: Switches the output status indicator
CN1:
 A. 1 - 8: Do11 - Do18, 9 - 16: Do21 - Do28
 B. 1 - 8: Do31 - Do38, 9 - 16: Do41 - Do48
CN2:
 A. 1 - 8: Do51 - Do58, 9 - 16: Do61 - Do68
 B. 1 - 8: Do71 - Do78, 9 - 16: Do81 - Do88

OUTPUT SPECIFICATIONS
Output: Open collector, 64 points
Isolation: Optical isolator
Common: All 8 points (8 terminals)
Common current: Max. 1 A per common
External excitation: 24 V DC ±10 %, approx. 0.04 A
Rated load voltage: 24 V DC ±10 %
Maximum load current: 0.1 A per point
Maximum rush current: 0.5 A for max. 10 msec.
Maximum leak current at OFF: 0.1 mA
Maximum voltage drop at ON: 0.1 V DC typical; 1.2 V DC max.
(When driving an inductive load, connect a diode in parallel with the load.)

INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE
Data allocation: 4
Current consumption: 160 mA
Response time: ≤ 2 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(Do 11 thru 18 to Do 21 thru 28 to Do 31 thru 38 to Do 41 thru 48 to Do 51 thru 58 to Do 61 thru 68 to Do 71 thru 78 to Do 81 thru 88)
2000 V AC @ 1 minute (output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

FUNCTIONS
OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
• Output Hold
If both are in error, the module holds the signal and stands by until one of the communications recovers.
• Output OFF
If both are in error, the module outputs OFF signals and stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is established and normal data is received.

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

OUTPUT CONNECTOR (40-pin)

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1069615
Online: 21
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965