R3-DA16B

Remote I/O R3 Series

AC CONTACT INPUT MODULE
(Di 16 points)

MODEL: R3–DA16B[1][2]

ORDERING INFORMATION
• Code number: R3-DA16B[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3-DA16BW/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

NO. OF CHANNELS
16: 16

INPUT
B: AC CONTACT INPUT

[1] COMMUNICATION MODE
S: Single
W: Dual

[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS
Connection
 Internal bus
: Via the Installation Base (model: R3-BSx)
 Input: M3 separable screw terminal (torque 0.5 N·m)
 Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
Isolation: Input to internal bus or internal power
Excitation monitor: Selectable with side DIP switch; ON/OFF setting available
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with excitation abnormality;
Green in normal operating conditions.
Input status indicator: Red LED; turns on with the input ON.

INPUT SPECIFICATIONS
Number of input: 16 points
Input voltage: 100 – 132 V AC
Input resistance: 12 kΩ (60 Hz), 15 kΩ (50 Hz)
Common: All points (2 terminals)
ON voltage/current: ≥ 80 V AC, ≥ 5 mA
OFF voltage/current: ≤ 30 V AC, ≤ 1.7 mA

INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE
Data allocation: 1
Current consumption: 80 mA
Response time: ≤ 0.1 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute
(input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive 
  EN 61010-1, EN 61010-2-201
  Measurement Category II (contact input)
  Pollution Degree 2
 Input to internal bus or internal power: Reinforced insulation (150 V) 
RoHS Directive
  EN 50581

FUNCTIONS
Excitation Monitor ON
The input is held at the last status when the loss of excitation is detected. The excitation must be connected across the terminal 9 (19) and 10 (20).
Excitation Monitor OFF
All input signals are turned off when the loss of excitation is detected.

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1069933
Online: 12
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965