R7LWTU MULTI POWER MODULE
Tình trạng: In stock
Contact: 0989649965
R7LWTU Remote I/O R7 Series MULTI POWER MODULE
Số lượt xem: 1567
Detail
·Some details are not shown. Please refer to specification sheets for all information.
R7LWTU
Remote I/O R7 Series
MULTI POWER MODULE
(Clamp-on current sensor CLSE, LonWorks)
ORDERING INFORMATION
• Basic module: R7LWTU-2[1]1-AD4[2]
Specify a code from below for each [1] and [2].
(e.g. R7LWTU-221-AD4/Q)
• Specify the specification for option code /Q
(e.g. /C01)
• Extension module: R7LWTU-EA8[1]
Specify a code from below for [1].
(e.g. R7LWTU-EA8/Q)
• Specify the specification for option code /Q
(e.g. /C01)
MODEL: R7LWTU-2[1]1-AD4[2]
CONFIGURATION
2: Single phase / 2-wire and 3-wire,
3-phase / 3-wire and 4-wire
[1] NO. OF SYSTEMS
1: 1 system, Di / Pi x 4 (internal power 5 V)
(no connection with extension module)
2: 2 systems
INPUT
1: 240 V AC / CLSE
POWER INPUT
Universal
AD4: 100 – 240 V AC / 110 – 240 V DC (universal)
(Operational voltage range 85 - 264 V AC, 50 - 60 Hz /
99 - 264 V DC, ripple 10 %p-p max.)
[2] OPTIONS
blank: none
/Q: With options (specify the specification)
EXTENSION MODULE: R7LWTU-EA8[1]
I/O TYPE
EA8: Di / Pi, 8 points (internal power 5 V)
[1] OPTIONS
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
FUNCTIONS & FEATURES
The R7LWTU is a Multi Power Module for LonWorks.
The R7LWTU uses clamp-on current sensors, there is no need of current transformers.
Current sensors are easy to install in existing systems. Wide input range of 5 to 600 A is availabe.
All measured values, counter values, display mode, setting data are stored in the non-volatile memory when power is off.
A ‘basic’ module can be attached with an ‘extension’ module (except R7LWTU-211-AD4)because of this, it is able to use it as 2-circuit power and 8 discrete inputs module.
RELATED PRODUCTS
• PC configurator software (model: PMCFG)
• XIF File (Device Interface File)
XIF file is used to define a LonWorks device when programmed on LonMaker.
The XIF files and Software are downloadable at M-System’s web site.
To connect the module to a PC a dedicated cable is required (refer to M-System's web site or instruction manual).
• Clamp-on current sensor (model: CLSE)
The clamp-on current sensors, not included in this product package, must be ordered separately. Required number depends upon the system configuration.
GENERAL SPECIFICATIONS
Connection: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the section.
Recommended manufacturer: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Configuration: Single phase/2-wire and 3-wire, 3-phase/3-wire balanced/unbalanced load, 3-phase/4-wire balanced/unbalanced load
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Sensor core to sensor output or current input or voltage input to discrete input to LonWorks or FG to power
Measured variables
Voltage: 1-N, 2-N, 3-N, 1-2, 2-3, 3-1
Current: 1, 2, 3, N
Active / reactive: Σ
Power factor: Σ
Frequency
Active energy: Incoming
Reactive energy: Incoming
Status indicator LED: PWR
LonWorks COMMUNICATION
Neuron Chip: FT3150
(NeuronID printed in numbers and bar code [peel-off code 39 format])
Transceiver: FT-X1 (equivalent to FTT10A)
Transmission speed: 78 kbps
Twisted-pair cable
Distance, free topology: 500 meters
Max. 64 nodes/channel
LNS: Ver. 3.0 Service Pack 8 or higher
Status indicator: ONLINE, ERR, TX/RX, SVCE (service)
Operation switch: Service, reset
INPUT SPECIFICATIONS
Frequency: 50 / 60 Hz (45 – 65 Hz)
• Voltage Input
Rated voltage
Line-to-line (delta voltage): 240 V
Line-neutral (phase voltage): 138 V
Consumption VA: ≤ ULN2 / 300 kΩ / phase
Overload capacity: 200 % of rating for 10 sec., 120 % continuous
Selectable primary voltage range: 50 – 400 000 V
• Current Input
CLSE-R5: 0 – 5 A AC
CLSE-05: 0 – 50 A AC
CLSE-10: 0 – 100 A AC
CLSE-20: 0 – 200 A AC
CLSE-40: 0 – 400 A AC
CLSE-60: 0 – 600 A AC
Overload capacity: 120 % continous, 500 % for 10 sec.
(Note: Use for the circuit not exceed 480 V)
Selectable primary current range: 1 – 20 000 A (only with CLSE-R5, refer to the configurator settings)
Operational range
Current: 0 – 120 % of the rating
Voltage: 10 – 120 % of the rating
Active/reactive power: ±120 % of the rating
Frequency: 45 – 65 Hz
Power factor: ±1
■ Discrete input
Common: Negative common
Maximum frequency: 10 Hz
Minimum pulse width: 50 msec.
Totalized pulse range: 0 - 9 999 999
Count at overflow: Reset and restart at ‘0.’
Detecting voltage/current: 5 V DC / 5 mA approx.
Detecting levels: ≤ 5 kΩ / ≤ 2 V for ON;
≥ 100 kΩ / 4 V for OFF
Operation mode: Discrete and pulse counter
INSTALLATION
Power consumption
•AC:
Basic module: < 5 VA
Basic with extension module: < 6 VA
•DC:
Basic module: < 1.5 W
Basic with extension module: < 2 W
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight:
Basic module: 200 g (0.44 lb)
Extension module: 90 g (0.2 lb)
PERFORMANCE
Accuracy (at 10 - 35°C or 50 - 95°F, 45 – 65 Hz)
Add the accuracy of the current sensor for overall values.
Voltage: ±0.5 % of the rating
Current: ±0.5 % of the rating
Power: ±1.0 % of the rating
Power factor: ±1.5 %
Energy: ±2.0 % of the rating (range 5 - 100 %, PF 1)
Frequency: ±0.1 % of the rating
The described accuracy levels are ensured at the input 1 % or more for phase 2 current with 3-phase/3-wire unbalanced load and for neutral current with 1-phase/3-wire.
Data update period:
Frequency: ≤ 1 sec.
Other: ≤ 500 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
2000 V AC @ 1 minute (current input or voltage input or discrete input to LonWorks or FG to input power)
1000 V AC @ 1 minute (current input or voltage input to discrete input)
EXTERNAL VIEW
TERMINAL CONNECTIONS
CONNECTION DIAGRAMS
TERMINAL ASSIGNMENTS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
M-System Co., Ltd.
Products
-
FAMCL-01 CC-Link MASTER MODULE
FAMCL-01 Remote I/O FAM Series CC-Link MASTER MODULE (Yokogawa Electric PLC use)
-
R5-MS POTENTIOMETER INPUT MODULE
R5-MS Remote I/O R5 Series POTENTIOMETER INPUT MODULE
-
R8-SS2 DC CURRENT INPUT MODULE
R8-SS2 Remote I/O R8 Series DC CURRENT INPUT MODULE (2 points, isolated)
-
R3-SS8 DC CURRENT INPUT MODULE
R3-SS8 Remote I/O R3 Series DC CURRENT INPUT MODULE (8 points, isolated)
-
R3-RS8 RTD INPUT MODULE
R3-RS8 Remote I/O R3 Series RTD INPUT MODULE (8 points, isolated)
-
R3-DC32A DISCRETE OUTPUT MODULE
R3-DC32A Remote I/O R3 Series DISCRETE OUTPUT MODULE (Do 32 points; open collector)
-
R30SV4 DC VOLTAGE/CURRENT INPUT MODULE
R30SV4 Remote I/O R30 Series DC VOLTAGE/CURRENT INPUT MODULE (4 points, isolated)
-
R3-DC16C DISCRETE OUTPUT MODULE
R3-DC16C Remote I/O R3 Series DISCRETE OUTPUT MODULE (PNP transistor output, 16 points)
-
R3-MS4 POTENTIOMETER INPUT MODULE
R3-MS4 Remote I/O R3 Series POTENTIOMETER INPUT MODULE (4 points, isolated)
PRODUCTS LIST
- Signal Conditioners
- 2-wire Signal Conditioners
- Power Transducers
- Indicators
- Tower Lights
- Limit Alarms
- Gateway, Remote IO
- Paperless Recording System
- PC Recorder
- Web Data Loggers
- PID Control Components
- BA&Energy Monitoring Components
- Temperature Controllers
- Electric Actuators
- Lightning Surge Protectors