R3-MS4 POTENTIOMETER INPUT MODULE

Share on FacebookShare on Google+Tweet about this on TwitterShare on LinkedIn

Tình trạng: In stock

Contact: 0989649965

R3-MS4 Remote I/O R3 Series POTENTIOMETER INPUT MODULE (4 points, isolated)

Số lượt xem: 1729

Detail

·Some details are not shown. Please refer to specification sheets for all information.

R3-MS4

Remote I/O R3 Series

POTENTIOMETER INPUT MODULE
(4 points, isolated)

MODEL: R3-MS4[1][2]

ORDERING INFORMATION
• Code number: R3-MS4[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3-MS4W/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01/SET)

INPUT
Total resistance 100 Ω - 20 kΩ

NO. OF CHANNELS
4: 4

[1] COMMUNICATION MODE
S: Single
W: Dual

[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-8401)

GENERAL SPECIFICATIONS
Connection
 Internal bus
: Via the Installation Base (model: R3-BSx)
 Input: M3 separable screw terminal (torque 0.5 N·m)
 Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
Isolation: Input 1 to input 2 to input 3 to input 4 to internal bus or internal power
Conversion rate: Selectable with the side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with input abnormality;
Green in normal operating conditions.

INPUT SPECIFICATIONS
Minimum span: 50 % of total resistance
Excitation: Approx. 0.2 V DC

INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE
Conversion accuracy: Refer to the table at the end of this section.
The resolution and conversion accuracy are defined against the potentiometer's total resistance.  If the actual resistance range (between the zero and span positions) is narrower than the total resistance, the values change in proportion.  Using at least 50 % of the total resistance is basically recommended.
Conversion rate: 80 / 40 / 20 / 10 msec. selectable
Data range: 0 – 10000
Data allocation: 4
Current consumption: Approx. 50 mA
Temp. coefficient: ±0.015 % /°C
Temperature coefficient is defined against the potentiometer's total resistance. If the actual resistance range (between the zero and span positions) is narrower than the total resistance, the values change in proportion. Using at least 50 % of the total resistance is basically recommended.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input 1 to input 2 to input 3 to input 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1061390
Online: 17
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965