MDM2A-24
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR FOR
STANDARD SIGNAL LINE & PULSE USE
(life monitor, 24 V DC line voltage)
Functions & Features
• Designed specifically for 4 – 20 mA DC and
pulse signal line including both 4-wire and 2-wire transmitters
• Absorbs surges only without affecting instrumentation signal
• Life monitor function helps you to decide when you should replace the surge protector; reduces maintenance and prevents downtime
• LED display and alarm contact output indicate the degradation and life span of the surge protection circuits
MODEL: MDM2A–24–[1]
ORDERING INFORMATION
• Code number: MDM2A-24-[1]
Specify a code from below for [1].
(e.g. MDM2A-24-M2)
[1] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Housing material: Flame-resistant resin (black)
Alarm indicators
PWR: The green LED turns on while the power is supplied.
ALM: Tricolor LED (green/amber/red)
· Remains off when the power supply is first turned on.
· Green: The unit has received one or more surges.
· Amber: Replacement is recommended.
· Red: The life span has ended.
Degradation judged: When the leakage current at the voltage limiter exceed approx. 7.5 μA.
Life time judged: When the number of discharges of the discharge element reaches the expected life span.
Alarm output: The N.C. contact is on when the life span of the discharge elements has ended, when the voltage limiter has degraded, and/or when the power supply is removed.
Rating: 125 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 125 V AC or 110 V DC
Maximum switching power: 62.5 VA or 30 W
Minimum load: 5 V DC @ 1 mA
INSTALLATION
Power consumption
•AC: Approx. 2 VA at 100 V
Approx. 3 VA at 200 V
Approx. 4 VA at 240 V
•DC: Approx. 1.5 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lb)
PERFORMANCE
Discharge voltage (peak voltage)
Line to line: 30 V min.
Line to ground: ±300 V min.
Maximum surge voltage
Line to line: 45 V max.
Line to ground: ±650 V max.
(The maximum voltage that could pass through M-RESTER. Protected equipment must be able to withstand this voltage for very short time period.)
Response time: ≤ 0.1 μsec.
Leakage current:
Line to line: ≤ 5 μA @ 30 V DC
Line to ground: ≤ 5 μA @ ±140 V DC
Discharge current capacity: 5000 A (8 / 20 μsec.)
Max. load current: 100 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
(surge protector circuit to alarm output to power)
Dielectric strength: 2000 V AC @ 1 minute
(surge protector circuit to power to ground)
Internal series resistance: 20 Ω ±10 % (including return)
Maximum line voltage: 30 V
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (alarm output)
Installation Category II (power)
Pollution degree 2
Surge protector circuit to power:
Reinforced insulation (300 V)
RoHS Directive
EN 50581
CONNECTION EXAMPLES
GROUNDING
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
M-System Co., Ltd.
Products
-
MD6N-65 LIGHTNING SURGE PROTECTOR FOR STANDARD SIGNAL LINE & PULSE USE
-
MD72WD LIGHTNING SURGE PROTECTOR FOR TWO-WIRE SIGNAL LOOP
-
MD72W LIGHTNING SURGE PROTECTOR FOR TWO-WIRE SIGNAL LOOP
-
MD6P-65 LIGHTNING SURGE PROTECTOR FOR STANDARD SIGNAL LINE & PULSE USE
-
MD6P-24 LIGHTNING SURGE PROTECTOR FOR STANDARD SIGNAL LINE & PULSE USE
-
MD6T-65 LIGHTNING SURGE PROTECTOR FOR STANDARD SIGNAL LINE & PULSE USE
-
MD6T-24 LIGHTNING SURGE PROTECTOR FOR STANDARD SIGNAL LINE & PULSE USE
-
MD73W LIGHTNING SURGE PROTECTOR FOR THREE-WIRE SIGNAL LOOP
-
MDP-65T Lightning Surge Protectors for Electronics Equipment M-RESTER
PRODUCTS LIST
- Signal Conditioners
- 2-wire Signal Conditioners
- Power Transducers
- Indicators
- Tower Lights
- Limit Alarms
- Gateway, Remote IO
- Paperless Recording System
- PC Recorder
- Web Data Loggers
- PID Control Components
- BA&Energy Monitoring Components
- Temperature Controllers
- Electric Actuators
- Lightning Surge Protectors
STATISTIC
Visitor: 1034248Online: 3