R6N-TS2

Remote I/O R6 Series

THERMOCOUPLE INPUT MODULE
(2 points, Screw terminal)

Functions & Features
• Accepts direct input from an thermocouple and provides an isolated, linearized DC signal compact size remote I/O module

MODEL: R6N–TS2[1]

ORDERING INFORMATION
• Code number: R6N-TS2[1]
Specify a code from below for [1].
  (e.g. R6N-TS2/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS
• PC configurator software (model: R6CON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS
Connection
 Internal bus
: Via the Installation Base (model: R6N-BS)
 Input: M3 screw terminals (torque 0.5 N·m) 
 Internal power: Via the Installation Base (model: R6N-BS)
Recommended solderless terminal: Max. 5.8 mm (0.23”)
wide; Ones with insulation sleeve do not fit.
Applicable wire size: 0.2 – 2.5 mm2
Housing material: Flame-resistant resin (black)
Isolation: Input 1 to input 2 to internal bus or internal power
Zero adjustments: PC programming
Span adjustments: PC programming
Input type: Selectable with the side DIP SW or PC programming
Burnout detection: Upscale or downscale selectable with the side DIP SW or PC programming
Linearization: Standard
Cold Junction Compensation: CJC sensor incorporated
Module address: Selectable with DIP and rotary switches on the side
Configuration mode: With DIP switches on the side panel
Power indicator: Green LED; Refer to the istruction manual for details.
Status indicator: Bi-color (red/green) LED;
Refer to the instruction manual for details.

INPUT SPECIFICATIONS
Thermocouple: K, E, J, T, B, R, S, C, N, U, L, P, PR
Input resistance: 30 kΩ min.
Burnout sensing: ≤ 0.1 μA

INSTALLATION
Current consumption: 20 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R6N-BS)
Weight: 60 g (2.1 oz)

PERFORMANCE
Conversion accuracy: ±1°C (±1.8°F) except ±2°C (±3.6°F) for B, R, S, C, PR
Conversion rate: 250 msec. / 500 msec.(PC programmable. Factory set to 500 msec.)
Converted data range:
•Engineering unit value (°C, K) × 10 (integer)
•Engineering unit value (°F)
Data allocation: 2
Cold junction compensation error:
±3°C at 25 ±10°C
±5.4°F at 77 ±18°F
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. span
Response time: Conversion rate × 2 + 50 msec. or less
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input 2 to internal bus or internal power to ground)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

EXTERNAL VIEW

Refer to the instruction manual for setting procedures.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1045316
Online: 6
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965