R6-NF1 T-Link INTERFACE MODULE

Share on FacebookShare on Google+Tweet about this on TwitterShare on LinkedIn

Tình trạng: In stock

Contact: 0989649965

R6-NF1 Remote I/O R6 Series T-Link INTERFACE MODULE

Số lượt xem: 1573

Detail

·Some details are not shown. Please refer to specification sheets for all information.

R6-NF1

Remote I/O R6 Series

T-Link INTERFACE MODULE
(Fuji Electric T-Link use)

Functions & Features
• Free combination of analog and discrete I/O
• Direct sensor inputs
• Space-saving
• Low power consumption
Typical Applications
• Remote I/O for DCS and PLC
 

MODEL: R6-NF1[1]

ORDERING INFORMATION
• Code number: R6-NF1[1]
Specify a code from below for [1].
  (e.g. R6-NF1/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS
• PC configurator software (model: R6CON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS
Connection
 
Network: Euro type connector terminal
  (applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm)
 Internal bus: Via the Installation Base (model: R6x-BSB)
 Internal power: Via the Installation Base (model: R6x-BSB)
Housing material: Flame-resistant resin (gray)
Isolation: T-Link to internal bus or internal power
I/O points: 4, 8, 16, 64 (side DIP switch)
I/O type: Input only, output only, input/output mixed (side DIP SW)
RUN indicator: Bi-color (green/red) LED; green in normal communications; red when receiving (Function selected with DIP SW)
ERR indicator: Bi-color (green/red) LED; the green ON/ blinks in communication errors; red when transmitting (Function selected with DIP SW)
Data allocation: Mode 1 or 2 set with the side DIP switch

T-Link SPECIFICATIONS
Station No. setting: Rotary switch; 00 – 99
Configuration: Multi-drop
Communication: Half-duplex
Baud rate: 500 kbps
Transmission media/distance:
  KPEV-SB, 0.75 mm2 × 1 pair, 700 m
  T-KPEV-SB, 1.25 mm2 × 1 pair, 1000 m

INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R6x-BSB)
 (Caution: Do NOT use other base but R6x-BSB)
Weight: 150 g (0.33 lb)

PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (T-Link to internal bus or internal power)

EXTERNAL VIEW

TRANSMISSION DATA DESCRIPTIONS
The DIP SW located at the side of the module switches the unit’s data allocation mode.
In the Data Allocation Mode 1, one (1) word is assigned for one I/O module. In this mode, analog I/O modules are used as single-channel types. Therefore, the second channel on the dual-channel modules cannot be used. The maximum number of modules connected to the network is 32.
In the Data Allocation Mode 2, two (2) words are assigned for one I/O module regardless of whether the second word area is required or not.

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

M-System Co., Ltd.

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1045171
Online: 2
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965