M2XT2 Super-mini Signal Conditioners Mini-M Series

THERMOCOUPLE TRANSMITTER
(PC programmable)

Functions & Features
• Accepts direct input from a thermocouple and provides a linearized process signal
• PC programmable
• Wide selection of thermocouples
• User’s temperature table can be used
• Leadwire resistance compensation
Typical Applications
• Small burnout sensing current enables long distance transmission with minimum offset drifts
• Electric furnace (isolation ensured even when 200 V AC power for heater leaks through furnace wall)
• No burnout type can connect to a single T/C in parallel with a recorder
• Ideal for quick spare part
 

MODEL: M2XT2–[1][2]-[3][4]

ORDERING INFORMATION
• Code number: M2XT2-[1][2]-[3][4]
Specify a code from below for each [1] through [4].
  (e.g. M2XT2-2Z1-M2/BL/CE/Q)
K thermocouple setting will be used if the input code is not specified.
• Temperature range (e.g. 0 – 800°C)
• Output range (e.g. 4 – 20 mA DC)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] INPUT THERMOCOUPLE
1: (PR)
2: K (CA)
3: E (CRC)
4: J (IC)
5: T (CC)
6: B (RH)
7: R
8: S
9: C (WRe 5-26)
N: N
U: U
L: L
P: P (Platinel II)
0: Specify
(Configurator software is used to change the input type and precise range.)

[2] OUTPUT
Current
Z1: Range 0 – 20 mA DC
Voltage
V1: Range -2.5 – +2.5 V DC
V2: Range -10 – +10 V DC
(Configurator software is used to change output over the described range of the selected suffix code. For changing out of this range, set the Output Range Selectors inside the unit before software adjustment.)

[3] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
(90 – 264 V for UL)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
(110 V ±10 % for UL)

[4] OPTIONS (multiple selections)
Burnout
blank: Upscale burnout
/BL: Downscale burnout
(UL not available)
/BN: No burnout
(UL not available)
Standards & Approvals (must be specified)
/N: Without CE or UL
/CE: CE marking
/UL: UL approval, CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating (UL not available)
TERMINAL SCREW MATERIAL
/S01: Stainless steel (UL not available)

RELATED PRODUCTS
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -15 to +115 %
(Negative current output is not provided.)
Manual zero/span adjustments: See Front View.
Programming: Downloaded from PC; T/C type, temp. range, output range, zero and span, simulating output, etc.
Burnout protection: Upscale standard; downscale or no burnout optional by programming
(Set to "no burnout" when the unit is connected with another instrument in parallel.)
Linearization: Standard
Cold junction compensation: CJC sensor attached to the
input terminals
Status indicator LED: Blinking patterns indicate different operating status of the transmitter.
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level

INPUT SPECIFICATIONS
Input resistance: 1 MΩ min.
Burnout sensing: 45 nA ±10 %
If not specified, the input range is shown below.
1 PR: 0–1600°C
2 K: 0–1000°C
3 E: 0–500°C
4 J: 0–500°C
5 T: 0–300°C
6 B: 0–1800°C
7 R: 0–1600°C
8 S: 0–1600°C
9 C: 0–2000°C
N N: 0–1000°C
U U: 0–300°C
L L: 0–500°C
P P: 0–1200°C

OUTPUT SPECIFICATIONS
 DC Current
Operational range: 0 – 24 mA DC
Output range: 0 – 20 mA DC
Minimum span: 1 mA
Offset: Lower range can be any specific value within the output range provided that the minimum span is maintained.
Load resistance: Output drive 15 V max.
(e.g. 4 – 20 mA: 750 Ω [15 V ÷ 20 mA])
If not specified, the output range is 4 – 20 mA DC.
DC Voltage
Code V1 (narrow spans)
Operational range
: -3 – +3 V DC
Output range: -2.5 – +2.5 V DC
Minimum span: 250 mV
Code V2 (wide spans)
Operational range: -11.5 – +11.5 V DC
Output range: -10 – +10 V DC
Minimum span: 1 V
Offset: Lower range can be any specific value within the output range provided that the minimum span is maintained.
Load resistance: Output drive 1 mA max.
(e.g. 1 – 5 V: 5000 Ω [5 V ÷ 1 mA])
If not specified, the output range is shown below.
V1: 0 – 1 V DC
V2: 1 – 5 V DC

INSTALLATION
Power Consumption
AC:
 Approx. 3 VA at 100 V
 Approx. 4 VA at 200 V
 Approx. 5 VA at 264 V
DC: Approx. 2 W
Operating temperature: -30 to +60°C (-22 to +140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 120 g (0.26 lb)

PERFORMANCE
Accuracy: [Table 1 Accuracy value + Cold Junction Compensation Error 0.5°C (0.9°F)] or ±0.1 % of span, whichever is greater.
 Add 0.2 % when the output span equals 1/10 or narrower of the max. span.
Cold junction compensation error:
±0.5°C at 25 ±10°C
±0.9°F at 77 ±18°F
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span at -5 to +55°C [23 to 131°F]
Response time: ≤ 0.9 sec. (0 – 90 %)
Burnout response: ≤ 10 sec.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output to power to ground)

CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example 1]
Input: K thermocouple, 0 – 1000°C, Output: 4 – 20 mA DC
1) Absolute value accuracy (Table 1): 0.25°C
2) CJC error (0.5°C) added: 0.75°C
3) 0.75°C ÷ 1000°C × 100 = 0.075 %
4) 0.075 % < 0.1 % of span. ➠ 0.1 % is selected.
5) Output span 16 mA (= 20 mA – 4 mA)
Max. span 20 mA
Output span ≥ 1/10 of max. span ➠ No need of adding
0.2 %.
6) Overall accuracy equals ±0.1 % of span
[Example 2]
Input: K thermocouple, 50 – 150°C, Output: 2.0 – 2.5 V DC
1) Absolute value accuracy (Table 1): 0.25°C
2) CJC error (0.5°C) added: 0.75°C
3) 0.75°C ÷ (150 – 50)°C × 100 = 0.75 %
4) 0.75 %> 0.1 % of span. ➠ 0.75 % is selected.
5) Output span 0.5 V (= 2.5 V – 2.0 V)
Max. span 5 V
Output span ≤ 1/10 of max. span ➠ Add 0.2 %.
6) Overall accuracy equals ±0.95 % of span (0.75 + 0.2)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive
  EN 61010-1
  Installation Category II
  Pollution Degree 2
  Input or output to power: Reinforced insulation (300 V)
  Input to output: Basic insulation (300 V)
RoHS Directive
  EN 50581
Approval:
UL/C-UL nonincendive Class I, Division 2,
  Groups A, B, C, and D
  (ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
  (UL 61010-1, CAN/CSA-C22.2 No.61010-1)

EXTERNAL VIEW

Refer to the instruction manual for detailed procedures.

EXTERNAL DIMENSIONS unit: mm (inch)

TERMINAL ASSIGNMENTS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM


M-system Vietnam
Email: sales@m-system.com.vn

Products

More

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1071620
Online: 23
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965