LSMT4 Power Transducer Series
MULTI POWER TRANSDUCER
Functions & Features
•
Measures simultaneously several variables of a heavy-current power
system: current, voltage, active, reactive and apparent power, active
and reactive energy, power factor, frequency, etc.
• Parameters are programmable using the front keys or the PC
• Displayed measurands are freely selectable
• Loop test output
• 10-point analog and 2-point energy pulse output
Typical Applications
• Multi-functional power measurement in electric device or in switching boards.
MODEL: LSMT4–[1][2][3]1–[4][5]
ORDERING INFORMATION
• Code number: LSMT4-[1][2][3]1-[4][5]
Specify a code from below for each [1] through [5].
(e.g. LSMT4-12A1-AD4/Q)
• Specify the specification for option code /Q
(e.g. /C01)
• Non-specified orders will be shipped at default factory settings (No. ESU-1957). However, the power suffix code must be specified.
Measured variables can be reconfigured with front panel or PC configurator software.
[1] CONFIGURATION
1: Single phase / 2-wire and 3-wire, 3-phase / 3-wire
2: Single phase / 2-wire and 3-wire,
3-phase / 3-wire and 4-wire
[2] INPUT
1: 480 V / 1 A AC
2: 480 V / 5 A AC
[3] OUTPUT
Current
A: 4 – 20 mA DC
Voltage
4: 0 – 10 V DC
5: 0 – 5 V DC
6: 1 – 5 V DC
DISCRETE OUTPUT
1: Do 2-point
[4] AUXILIARY POWER SUPPLY
AD4: universal
100 – 240 V AC (Operational range 85 – 264 V, 50 / 60 Hz) /
110 – 240 V DC (Operational range 99 – 264 V,
ripple 10 %p-p max)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
V: 48 V DC
(Operational voltage range 48 V ± 10 % , ripple 10 % p-p max.)
[5] OPTIONS
blank: none
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
Products
-
54UC MULTI POWER MONITOR
54UC MULTI POWER MONITOR 110 x 110 mm panel size Robust screw terminal connection Four digital displays 60-segment bargraph Single-phase/2-wire and 3-wire, three-phase/3-wire and 4-wire systems All measured variables can be transmitted to the host PC via RS-485/Modbus RTU or CC-Link,LONWORKS Energy count pulse or limit alarm output selectable Up to 4 optional analog outputs Programming lock to prevent unwanted configuration changes Input range up to 480 Vac, 1 A or 5 A Modbus:54U CC-Link:54UC LONWORKS:54UL
-
L53U MULTI POWER TRANSDUCER
L53U MULTI POWER TRANSDUCER Single type module is usable for all of single-phase/2-wire and 3-wire, three-phase/3-wire and 4-wire systems. All measured variables can be transmitted to the host PC via RS-485/Modbus RTU. Energy count pulse or limit alarm output selectable Up to 4 optional analog outputs Remote and local programming using the PC Configurator Software Input range up to 480 Vac, 1 A or 5 A DIN rail mounted
-
54UL MULTI POWER MONITOR
54UL MULTI POWER MONITOR 110 x 110 mm panel size Robust screw terminal connection Four digital displays 60-segment bargraph Single-phase/2-wire and 3-wire, three-phase/3-wire and 4-wire systems All measured variables can be transmitted to the host PC via RS-485/Modbus RTU or CC-Link,LONWORKS Energy count pulse or limit alarm output selectable Up to 4 optional analog outputs Programming lock to prevent unwanted configuration changes Input range up to 480 Vac, 1 A or 5 A Modbus:54U CC-Link:54UC LONWORKS:54UL
-
54U - MULTI POWER MONITOR
54U - MULTI POWER MONITOR 110 x 110 mm panel size Robust screw terminal connection Four digital displays 60-segment bargraph Single-phase/2-wire and 3-wire, three-phase/3-wire and 4-wire systems All measured variables can be transmitted to the host PC via RS-485/Modbus RTU or CC-Link,LONWORKS Energy count pulse or limit alarm output selectable Up to 4 optional analog outputs Programming lock to prevent unwanted configuration changes Input range up to 480 Vac, 1 A or 5 A Modbus:54U CC-Link:54UC LONWORKS:54UL
-
53U Power Monitor
53U Power Monitor
PRODUCTS LIST
- Signal Conditioners
- 2-wire Signal Conditioners
- Power Transducers
- Indicators
- Tower Lights
- Limit Alarms
- Gateway, Remote IO
- Paperless Recording System
- PC Recorder
- Web Data Loggers
- PID Control Components
- BA&Energy Monitoring Components
- Temperature Controllers
- Electric Actuators
- Lightning Surge Protectors
STATISTIC
Visitor: 3486803Online: 23