CLSD CLAMP-ON CURRENT SENSOR

Share on FacebookShare on Google+Tweet about this on TwitterShare on LinkedIn

Tình trạng: In stock

Contact: 0989649965

CLSD CLAMP-ON CURRENT SENSOR Easy-to-install, clamp-on type current sensor Over-voltage clamp element for safety in open circuit 1A Output

Số lượt xem: 1280

Detail

CLSD CLAMP-ON CURRENT SENSOR
(1A output)

Functions & Features
•Easy-to-install, spring-loaded, clamp-on type current sensor
•Over-voltage clamp element for safety in open circuit
•1 A output

MODEL: CLSD–[1]-[2]-1

ORDERING INFORMATION
• Code number: CLSD-[1]-[2]-1
Specify a code from below for each of [1] and [2].
  (e.g. CLSD-A-15-1)
Special specifications are possible. Consult factory.
  (Input: 100 to 2000 A, Output: 1 A or Input: 500 to 2000 A, Output: 5 A)

[1] INTERNAL DIAMETER
A: 24 (Select 15 or 20 for Input suffix code.)
B: 36 (Select 30 or 40 for Input suffix code.)
C: 60 ( Select 80 or 100 for Input suffix code.)
D: 100 (Select 200 for Input suffix code.)

[2] INPUT
15: 150 A
20: 200 A
30: 300 A
40: 400 A
80: 800 A
100: 1000 A
200: 2000 A

OUTPUT
Current
1: 1 A

CAUTION
Before you remove the sensor module or mount it, turn off the input signal for safety. While the line is alive, the module’s cores, attracted to each other, may be hard to separate.

RELATED PRODUCTS
AC current, watt, power factor transducers with 1 A input
•CT input module (model: R3-CT4)
•Multi power input module (model: R3-WT1)
•AC power input module (model: R3-WT4)
•AC current transducer (model: 14CE)
•AC current transducer (model: LTCE)
•CT transmitter (model: CT)
•CT transmitter (model: KCE)
•CT transmitter (model: M2CE)
•CT converter (model: M8CT)
•CT transmitter (model: M5CT)
•Multi power monitor (model: 53U, 54U, 54UC, 54UL)

GENERAL SPECIFICATIONS
Construction: Clamp
Housing material: Flame-resistant resin (black)
Applicable wire: Min. 0.75 mm2
Output clamp voltage: ±1.4 Vp-p

INPUT SPECIFICATIONS
Max. working voltage: 480 V AC (primary side)
Overload capacity: 120 % continuous, 4000 % for 1 minute
Operational range
CLSD-A-15: ≤ 150 A
CLSD-A-20: ≤ 200 A
CLSD-B-30: ≤ 300 A
CLSD-B-40: ≤ 400 A
CLSD-C-80: ≤ 800 A
CLSD-C-100: ≤ 1000 A
CLSD-D-200: ≤ 2000 A

INSTALLATION
Operating temperature: -20 to +60°C (-4 to +140°F)
Operating humidity: 85 % RH max. (non-condensing)
Mounting: Fix with a binding strap.
Weight
  CLSD-A: 230 g (0.51 lb)
  CLSD-B: 350 g (0.77 lb)
  CLSD-C: 500 g (1.1 lb)
  CLSD-D: 950 g (2.1 lb)

PERFORMANCE
Rated primary current / rated secondary current
  CLSD-A-15: 150 A / 1 A
  CLSD-A-20: 200 A / 1 A
  CLSD-B-30: 300 A / 1 A
  CLSD-B-40: 400 A / 1 A
  CLSD-C-80: 800 A / 1 A
  CLSD-C-100: 1000 A / 1 A
  CLSD-D-200: 2000 A / 1 A
Rated VA: 0.5 VA
Frequency: 50 / 60 Hz
Ratio error: ±1.0 %, 1.0 In / ±1.5 %, 0.2 In
Phase displacement error: ±80', 1.0 In / ±120', 0.2 In
Insulation resistance: ≥ 100 MΩ with 500 V DC
(sensor core to output)
Dielectric strength: 2000 V AC @ 1 minute
(sensor core to output)

EXTERNAL DIMENSIONS mm (inch)

M-System Việt Nam

Email: Sales@m-system.com.vn

PRODUCTS LIST

News Product

WL40VN Series - 920 MHz Band Wireless I/O (for use in Vietnam)
Wireless Tower Light (FCC Part 15 compliant wireless module) IT40SW5F/6F, IT50SW5F/6F, IT60SW5F/6F Series
TR30-G Tablet Recorder  Web-enabled DAQ System
News

STATISTIC

Visitor: 1061816
Online: 16
0989649965
Sales@m-system.com.vnFacebook: M-System.com.vnZalo: 0989649965