R30YS4 DC CURRENT OUTPUT MODULE
Tình trạng: In stock
Contact: 0989649965
R30YS4 Remote I/O R30 Series DC CURRENT OUTPUT MODULE (4 points, isolated)
Số lượt xem: 2162
Detail
·Some details are not shown. Please refer to specification sheets for all information.
R30YS4
Remote I/O R30 Series
DC CURRENT OUTPUT MODULE
(4 points, isolated)
Functions & Features
• 4 channels for DC current output remote I/O module
• Isolation between output channels
MODEL: R30YS4S[1]
ORDERING INFORMATION
• Code number: R30YS4S[1]
Specify a code from below for [1].
(e.g. R30YS4S/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
4: 4
COMMUNICATION MODE
S: Single
[1] OPTIONS
blank: none
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-9006)
RELATED PRODUCTS
• PC configurator software (model: R30CFG)
Downloadable at M-System’s web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R30BS)
Output: M3 separable screw terminal (torque 0.5 N·m)
Internal power supply: Via the Installation Base (model: R30BS)
Solderless terminal: Refer to the drawing at the end of the section.
Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
(Solderless terminals with insulation sleeve do not fit.)
Applicable wire size: 0.25 to 0.75 mm2
Screw terminal: Nickel-plated steel
Isolation: Output 1 to output 2 to output 3 to output 4 to internal bus or internal power
Output at the loss of communication: Selectable with PC configurator software (Model: R30CFG, factory default: output hold)
Status indicator LED: RUN, ERR
(refer to the instruction manual)
OUTPUT SPECIFICATIONS
Module type: Analog output, 4 points
Output range: 4 to 20 mA DC
Load resistance: ≤ 550 Ω
Operational range: -15 to +115 % of output range
INSTALLATION
Current consumption: 120 mA max.
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 160 g (0.35 lb)
PERFORMANCE
Conversion accuracy: ±0.1 %
Conversion rate: 10 msec.
Data range: 0 – 10000 of the output range
Data allocation: 4
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Output delay time: ≤ 250 ms (0 - 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (output 1 to output 2 to output 3 to output 4 to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated by the power supply module)
FUNCTIONS
■ Output at the loss of communication
• Output Hold
If the network module is in error, the module holds the signal at error and stands by until the communication recovers.
• Output set value
If the network module is in error, the module holds the signal at error or power up and stands by until the communication recovers. The the signal at error or power up is selectable with PC configurator software (Model: R30 CFG)
Not depending on output at the loss of communication setting, when power up the module holds the signal at error or power up and stands by until the normal data is received.
■ OUTPUT WIRE BREAKDOWN DETECTION
In the case of wire breakdown, output error is detected.
Then, the ERR indicator LED blinks in red and the flag of error is set on the PLC etc.
PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R30CFG)
Refer to the users manual for the R30CFG for detailed operation of the software program.
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
M-System Co., Ltd.
Products
-
FAMCL-01 CC-Link MASTER MODULE
FAMCL-01 Remote I/O FAM Series CC-Link MASTER MODULE (Yokogawa Electric PLC use)
-
R5-MS POTENTIOMETER INPUT MODULE
R5-MS Remote I/O R5 Series POTENTIOMETER INPUT MODULE
-
R8-SS2 DC CURRENT INPUT MODULE
R8-SS2 Remote I/O R8 Series DC CURRENT INPUT MODULE (2 points, isolated)
-
R3-SS8 DC CURRENT INPUT MODULE
R3-SS8 Remote I/O R3 Series DC CURRENT INPUT MODULE (8 points, isolated)
-
R3-RS8 RTD INPUT MODULE
R3-RS8 Remote I/O R3 Series RTD INPUT MODULE (8 points, isolated)
-
R3-MS4 POTENTIOMETER INPUT MODULE
R3-MS4 Remote I/O R3 Series POTENTIOMETER INPUT MODULE (4 points, isolated)
-
R30SV4 DC VOLTAGE/CURRENT INPUT MODULE
R30SV4 Remote I/O R30 Series DC VOLTAGE/CURRENT INPUT MODULE (4 points, isolated)
-
R3-DC32A DISCRETE OUTPUT MODULE
R3-DC32A Remote I/O R3 Series DISCRETE OUTPUT MODULE (Do 32 points; open collector)
-
R3-NE1 ETHERNET INTERFACE MODULE
73VR1100 Series 73VR3100 Series PC Recorder Series R3 Series R3 Series for Power Monitoring
PRODUCTS LIST
- Signal Conditioners
- 2-wire Signal Conditioners
- Power Transducers
- Indicators
- Tower Lights
- Limit Alarms
- Gateway, Remote IO
- Paperless Recording System
- PC Recorder
- Web Data Loggers
- PID Control Components
- BA&Energy Monitoring Components
- Temperature Controllers
- Electric Actuators
- Lightning Surge Protectors
STATISTIC